Turkish Journal of Electrical Engineering and Computer Sciences
DOI
10.3906/elk-1504-189
Abstract
The existence of ultrahigh voltage direct-current (UHVDC) transmission lines impacts geoelectric field observation (GFO), which further disturbs earthquake observation and prediction. We proposed a mathematic method based on a 3-dimensional layered soil model to calculate the interference and conducted GFO experiments at observatories and field observation sites during the live debugging of a $\pm $800 kV UHVDC transmission line to verify the method. The results obtained by using the proposed method are in good accordance with the experimental results and the maximum error is no more than 15%. Moreover, the experiment proves that grounding current is a decisive factor in the interference from a transmission line to GFO.
Keywords
Ultrahigh voltage direct-current transmission line, geoelectric field observation interference, grounding current, 3-dimensional complex layered soil model, interference experiments of geoelectric field observation
First Page
5078
Last Page
5089
Recommended Citation
TANG, BO; WU, ZHUO; LIU, REN; WANG, SHUANG; and LIN, QIXIANG
(2016)
"Interference in geoelectric field observation from the current of a direct-current grounding electrode,"
Turkish Journal of Electrical Engineering and Computer Sciences: Vol. 24:
No.
6, Article 39.
https://doi.org/10.3906/elk-1504-189
Available at:
https://journals.tubitak.gov.tr/elektrik/vol24/iss6/39
Included in
Computer Engineering Commons, Computer Sciences Commons, Electrical and Computer Engineering Commons